|
Rapidlogger Oilfiled Technology
Rapidlogger monitoring system

(713) 574-1052

websales@rapidlogger.com

10700 Corporate Drive, Suite 108
Stafford, Texas 77477

Support – Tech Note 62

Using Rapidlogger with Micromotion Coriolis Flow Meter

This tech note describes the process to connect a Micro-Motion flow meter transmitter with a Rapidlogger system. The Micro-Motion has milli-ampere and frequency outputs.

Micro Motion Coriolis Meter
Rapidlogger Unit

Image 1 and 2: Micro-Motion Coriolis Meter Display And Rapidlogger Unit

It is important to note that the Rapidlogger CAN NOT be used to power the densitometer, you must use a separate power source for it. Acceptable voltages are 18 to 100 VDC or 85-265 VAC.

The milliamp output on the Micromotion carry the density signal. This should be wired to the Rapidlogger mA3 input.

The flow rate output of the Micromotion unit is generally configured to be on its Frequency output. On the Micromotion, the measured variable that is assigned to the frequency output should be “Volume Flow”. The pulse/pause ratio should be setup to the default value “1:1”. The output frequency should be set to the default value of “10000Hz”. The dampening should be set to the default value of “1sec”.

If the user wants to feed the Micromotion frequency signal to the Rapidlogger. It should be wired in to the Quadrature input of the Rapidlogger. The connections should be wired as shown in table 1.

Micromotion Terminal   Rapidlogger Terminal
1 mA + TB1-14 mA3 Input
2 mA – TB1-8 DC Ground
3 Frequency + TB1-16 Q1A input
4 Frequency – TB1-10 DC Ground
9 Power – NA NA
10 Power + NA NA

Table 1: Micro-Motion Wired to Rapidlogger Quadrature Input

Figure 3: Micro-motion Signal Wiring Terminal Blocks
Figure 3: Micro-motion Signal Wiring Terminal Blocks
Figure 4: Micromotion Power Input Terminal Blocks
Figure 4: Micromotion Power Input Terminal Blocks